A-type Residual Current Relay ASJ20-LD1A
description1
description2
General
ASJ series residual current operated relay can be combined with low voltage circuit breaker or low voltage contactor to form a residual current protection device, which is mainly used for the TT and TN system distribution lines with AC 50Hz and rated voltage of 400V and below. It is used to protect the electrical circuit form ground faults, prevent equipment damage caused by earth fault current and electrical fire accidents, and can also be used to provide indirect contact protection against personal electric shock hazard.
Products meet the requirements of GB/T 22387-2016 residual current operated relay.
LCD Display
Feature

Frequency
50Hz±5Hz
Auxiliary power supply
AC110V, AC220V, DC85 ~270V
(permissible error ±10%)
Installation
DIN Rail 35mm
Dimension(L*W*H)
85*54*64mm
● A-type residual current measurement
● Current percentage light column display
● Rated residual operating current can be measured
● Limit non-driving time can be set
● Two sets of relay output (settable)
● With local and remote “test” and “reset” functions

Parameter
Technical Parameter |
Indicator | |
A type | ||
Power supply |
Voltage range |
AC/DC85~265V |
Power dissipation |
≤5W |
|
Input |
Rated residual operating current I△n |
0.03, 0.05, 0.1, 0.3, 0.5, 1, 3, 5, 10 , 30(A)note 3 |
Limit non-driving time △t |
0, 0.06, 0.1, 0.2, 0.3, 0.5, 0.8, 1 ,4 , 10(s)note 4 |
|
Rated residual non-operating current I△no |
50%I△n |
|
Performance characteristics |
Sinusoidal AC and pulsating DC |
|
Frequency |
50Hz±5Hz |
|
Operating range |
-20% ~ -10%I△n |
|
Output |
Output mode |
One is normally closed or open, and another is for transformation |
Contact capacity |
AL1:8A 250VAC; 5A 30VDC AL2:6A 250VAC; 5A 30VDC |
|
Reset mode |
Local reset, remote reset or automatic reset |
|
Installation and use environment |
Humidity |
≤95%RH ,no condensation, and no corrosive gas places |
Elevation |
≤2000m | |
Class of pollution |
Grade three | |
Installation category |
Type Ⅲ | |
Dimension

type |
Panel size (mm) |
Shell size (mm) |
Hole size (mm) |
ASJ20 |
48*48 (Width*Height) |
43.8*43.8*100 (width*height*depth) |
45*45 (Width*Height) |
Diagram
Application
Packing&delivery

Product Selection
Type |
Function |
Installation |
Appearance |
ASJ10-LD1C |
AC-type residual current measurement; Alarm prompt of current crossing line; Rated residual operating current can be measured; Limit non-driving time can be set; Two sets of relay output; With local and remote “test” and “reset” functions. |
Guide (DIN 35mm) |
|
ASJ10-LD1A |
A-type residual current measurement; Current percentage light column display; Rated residual operating current can be measured; Limit non-driving time can be set; Two sets of relay output (settable); With local and remote “test” and “reset” functions. |
|
|
ASJ10L-LD1A |
A-type residual current measurement; Rated residual operating current can be measured; Limit non-driving time can be set; Two sets of relay output (settable); Transformer breakage alarm can be set; Pre-alarm value can be set; Return value can be set. With on-site display, remote "test", "reset" LCD display, 25 event records. |
|
|
ASJ20-LD1C |
AC-type residual current measurement; Alarm prompt of current crossing line; Rated residual operating current can be measured; Limit non-driving time can be set; Two sets of relay output; With local and remote “test” and “reset” functions. |
Panel (48*48) |
|
ASJ20-LD1A |
A-type residual current measurement; Current percentage light column display; Rated residual operating current can be measured; Limit non-driving time can be set; Two sets of relay output (settable); With local and remote “test” and “reset” functions. |
|